IEC 61850 Test System relay tester
Model:RELAYSTAR-6000D
Unique:
1)Embedded industrial PC with 9.7 inches touch screen
2)Both local test and remote test available
3)To simulate various type of messages which conform to IEC 61850-9-1/9-2, GOOSE, IEC 60044-7/8 FT3
4)12 low level analog outputs
5)Built-in GPS module
6)Lighter weight:only 4kg / 8.82lb
IEC 61850 SMV GOOSE MMS signal analyzer and smv create for intelligent substation relay protection system relay tester
Main Features:
1)Both local test and remote test available
2)Embedded industrial PC with 9.7 inches touch screen
3)Complete optical ports: 16 fiber optical ports, 8 channels for FT3 sending and 2 channels for receiving
4)Unique twisted-pair port monitoring function
5)Able to provide various type of messages which conform to IEC 61850-9-1/9-2, GOOSE , IEC 60044-7/8 FT3
6)Able to test MU and optical digital signal
7)Network analyzer function: capture the data packet of IEC 61850 or FT3, display and record the waveform, and simulate frame loss and gibberish during output.
8)Able to parse SCL(SCD,ICD,CID) file completely and configure SV, GOOSE message automatically
9)Multiple time synchronization modes: PPS, IRIG-B code, IEEE1588
10)Viewing sampled values: multi-meter and oscilloscope view
11)12 low level analog outputs
12)Built-in GPS module
IEC 61850 SMV GOOSE MMS signal analyzer and smv create for intelligent substation relay protection system relay tester
Main Functions:
RELAYSTAR-6000D is protection test system dedicated to IEC 61850, which is easy to carry due to small size and light weight(only 4kg / 8.82lb). It focuses on the real-time communication of GOOSE and Sampled Values to interface with the devices under test. Beyond this, it supports GPS/IRIG-B/IEEE 1588 synchronization, which makes both substation internal debugging and substation to substation joint debugging available. This test set is controlled by HAOMAI's powerful new software.
relay tester Technical Parameters:
Ethernet Communication Interfaces
Mode | 10/100Base-TX(10/100Mbit,twisted-pair,auto-crossover) |
Number of port | 2 |
Type of interface | RJ45 |
Status indication | LED lights |
Optical Fiber Communication Interfaces
Mode | 100Base-FX (100Mbit, optical fiber, full duplex) |
Number of port | 16 |
Type of interface | ST |
Fiber type | 62.5/125μm (multi-mode fiber) |
Wavelength | 1310nm |
Transmission distance | >1km |
Status indication | LED lights |
FT3 Interfaces
Number of port | 10 (8 for transmitter, 2 for receiver) |
Type of interface | ST |
Fiber type | 62.5/125μm (multi-mode fiber) |
Wavelength | 850nm |
Low Level Signal Analog Output
Number of outputs | 12 |
Setting range | AC: 0~7.07Vrms; DC: 0~10V |
Current at max. burden | 1mA |
Accuracy | <0.05% |
Resolution | 250μV |
Distortion (THD+N) | <0.1% |
Frequency | Sinusoidal signal: 10~1000Hz |
Transient signal: DC~10.0kHz | |
Accuracy: <0.002%(under power frequency, error 1mHz) | |
Resolution: 0.001Hz | |
Phase | Range of phase angle: 0 ~359. 9° |
Accuracy: <0.1°, 50/60Hz | |
Resolution: ±0.01° |
Binary Inputs
Number | 10 |
Type | potential-free contact or idle contact (automatic identification) |
Threshold characteristics | "0": 0~6V; "1":12V~250V |
Binary Outputs
Number | 4 |
Type | idle contact (fast contact output optional) |
Break capacity | 250VAC/0.5A; 250VDC/0.2A |
Power Supply
Nominal input voltage | customized (AC 220V/230V/120V/127V±10%, 1-phase) |
Nominal frequency | 50/60 Hz |
Rated current | 10A at 230V |
Connection | Standard AC socket (IEC 60320) |
Environmental Conditions
Operation temperature: 0 ... +50 °C (+32 ... +122 °F)
Storage temperature:-25 ... +70 °C (-13 ... +158 °F)
Humidity range: relative humidity 5 ... 95 %, non-condensing
Vibration: IEC 60068-2-6(20m/s2 at 10 ... 150 Hz)
Miscellaneous
Weight | 4kg(8.82 lb) |
Dimensions (W x H x D, without handle) | 345×135×270mm(13.58x5.31x10.63 in) |
Safety Standards, Electromagnetic Compatibility
EMC | The product adheres to the electromagnetic compatibility (EMC) Directive 2004/108/EC(CE conform). |
IEC 61326-1; IEC 61000-6-4; IEC 61000-3-2/3 | |
Safety | The product adheres to the low voltage Directive 2006/95/EC(CE conform). |
IEC 61010-1 |